Your documents basket contains 0 items
Operating voltage KNX | Bus voltage, ≤7.5 mA |
Max. valve stroke | 8 mm |
Runtime | <20 s/mm |
Installation type | Locks on valve adapter |
Type of connection | 6-pole (length 1.0 m) |
Behaviour in case of control signature failure | Moves to optional position |
Ambient temperature | 5°C ... 50°C |
Stock temperature | -20°C ... 60°C |
Medium temperature | ≤100°C |
Dimensions | 50 mm, 82 mm, 65 mm |
Protection class | III according to EN 60730-2-14 |
Type of protection | IP 21 |
Hand book | CHEOPS S KNX (1,6 MB) | |
Operating instructions | CHEOPS S KNX (3,3 MB) | |
KNX-Database (Single Product) | ZIP | CHEOPS S KNX (293,4 kB) |
KNX overall database KNXprod | ZIP | KNXprod (21,1 MB) |
Data sheet | CHEOPS S KNX (480,3 kB) | |
Catalogue | General catalogue 2024 (25,6 MB) |