Your documents basket contains 0 items
Operating voltage | 230 V AC |
Frequency | 50 Hz |
Installation height | 2 - 4 m |
Minimum height | 1.7 m |
Installation type | Ceiling mounting |
Colour | White |
Light measurement | Mixed light measurement |
Setting range brightness | 30 - 3000 lx |
Light switch-off delay | 10 s - 60 min |
Lamp types | Incandescent/halogen lamps, fluorescent lamps, Energy saving lamps, LEDs |
Incandescent/halogen lamp load | 2300 W |
Inrush current | max. 400 A / 200 µs |
LED lamp < 2 W | 25 W |
LED lamp 2-8 W | 250 W |
LED lamp > 8 W | 250 W |
Type of connection | Screw terminals |
Max. cable cross section | max. 2 x 2,5 mm² |
Switching output | Light |
Detection range | 50 m² (ø 8 m | 360°) |
Detection angle | 360° |
Ambient temperature | -15°C ... 50°C |
Impact resistance | IK04 |
Type of protection | IP 54 (when fitted) |
Mounting height (A) | Sitting (S) | Diagonally (T) | Head on to (R) |
2 m | 5 m² | 2.5 m | 38 m² | 7 m | 5 m² | 2.5 m |
2.5 m | 7 m² | 3 m | 38 m² | 7 m | 7 m² | 3 m |
3 m | 13 m² | 4 m | 50 m² | 8 m | 13 m² | 4 m |
3.5 m | 50 m² | 8 m | 13 m² | 4 m | |
4 m | 64 m² | 9 m | 13 m² | 4 m |
Tender text | DOC | theRonda S360-100 FLAT DE WH (55,6 kB) |
Operating instructions (Smartphone) | theRonda S360-100_mobil (1,5 MB) | |
Operating instructions | theRonda S360-100 (1,6 MB) | |
Data sheet | theRonda S360-100 FLAT DE WH (800,9 kB) | |
BIM data | Open planning data in web app |
Your documents basket contains 0 items